MUK HIU – Heat Network Sizing CIBSE & DS 439
Monso MEP Engineering UK LtdMUK HIU – Heat Network Sizing CIBSE & DS 439
Monso MEP Engineering UK LtdSize LTHW heat network pipework to HIUs in Autodesk® Revit® with CIBSE DS 439 diversity: flow and return, index circuit, pump duty, loss map, automatic sizing and a professional PDF report.
$299.00/year
MUK HIU sizes and checks the LTHW (low temperature hot water) pipework of heat networks and communal heating systems drawn in Revit, from the plant room to every Heat Interface Unit (HIU), following CIBSE & DS 439 (CP1 Heat Networks: Code of Practice for the UK).
With one click MUK HIU follows the flow and return pipework from the first pipe you pick, finds every HIU, adds up the loads downstream of each pipe and applies the diversity:
• Domestic hot water – DS 439 diversity factor k = 0.0316 + 0.5·N^-0.5 + 0.468·N^-1 applied to the DHW loads downstream.
• Space heating – fixed percentage or the variable factor 0.62 + 0.38/N.
• Flow and return are calculated together, each with its own water temperature; the design ΔT comes from your supply and return temperatures.
• Pressure loss with Darcy-Weisbach and the Haaland friction factor (64/Re in laminar flow), plus an optional allowance for fittings.
WHAT YOU GET
• Check – verifies the pipe sizes you have drawn against your maximum velocity and maximum pressure loss per metre.
• Size – gives every flow and return pipe the smallest size that complies (minimum DN15 by default) and updates the model, reconnecting any valves and fittings Revit releases.
• Index circuit – the most unfavourable HIU: flow + HIU pressure drop + return, highlighted in red, with the pump duty (flow rate and head).
• Loss map – every pipe coloured green / amber / red by its loss per metre.
• MUK DS439 panel – docked next to Properties: results of any pipe, fitting or HIU you select, and a table of every section that selects the pipe in the model when you click it.
• PDF report – your company logo and project data in the header, design criteria, building and per-level loads, HIU schedule by power, HIU circuits grouped by level, index circuit with the final sum, every pipe section, pump duty box, static pressure and system water content. Ready to issue. It now includes three 3D views drawn from your model: flow and return with every section reference (F1, R1…), the index circuit and the pressure loss map.
• Sample model with 12 HIUs on 3 levels and a ready-made MUK_HIU valve family (13 types, flow on top and return below) to copy into your projects.
• Project data shared with MUK GAS, so the same header is used in both reports.
Revit's own pipe calculations are not changed: MUK HIU works as a separate layer and only changes pipe sizes when you press Size.
Includes an illustrated user manual (press F1 on the ribbon buttons). 1-month (30-day) free trial, then annual subscription.
Results must be checked by a competent heating engineer.
Details
Frequently asked questions (FAQs)
What else should I know about this product?
Standards and references: CIBSE DS 439 (CP1 Heat Networks: Code of Practice for the UK), CIBSE Guide C. Units: kW, l/s, m/s, Pa/m, kPa, °C. Water properties at the flow and return temperatures. The licence check sends only your Autodesk user ID to Autodesk.
Are there any known issues with this product?
When Size changes a pipe diameter, Revit may disconnect valves and fittings; MUK HIU reconnects them and reports how many, so check the HIU valves and fittings afterwards. Height differences are not included in the pressure calculation (static pressure is reported separately).
Is there additional support information provided?
E-mail monsomepengineering@gmail.com (Monso MEP Engineering UK Ltd, London). We reply within two working days. Please include your Revit version, a screenshot of the MUK DS439 panel and, if possible, the PDF report.
Found an issue?